1. Home
  2. Half-cell potential testing

Test method · ASTM C876

Half-cell potential testing and corrosion mapping (ASTM C876)

Half-cell potential mapping measures the electrical potential of the reinforcing steel at a grid of points on the concrete surface. The map shows where corrosion is likely active, including areas with no visible damage yet.

  • Copper/copper sulfate electrode (CSE)
  • Measured grid tied to your drawings
  • Read with chloride and carbonation data

How the test works

We make a connection to the rebar and confirm the bars are electrically continuous. Then we take readings with a copper/copper sulfate reference electrode on a measured grid, with the spacing chosen for the element, often 1 to 2 ft. The surface is pre-wetted so the readings are stable.

The readings are plotted as a contour map over your drawings, so the areas at risk can be located on site and carried straight into repair documents.

Reading the results

ASTM C876 gives a numeric guide for readings against a copper/copper sulfate electrode:

Potential (mV vs CSE)Probability of corrosion
More positive than −20090% probability that no corrosion is occurring
−200 to −350Corrosion activity uncertain
More negative than −35090% probability that corrosion is occurring

The numbers are a guide, not a verdict. Moisture, oxygen, concrete cover and coatings all shift the readings, so we also read the map for gradients, where potentials drop sharply over a short distance, and confirm with chloride and carbonation results and a few exploratory openings.

Where half-cell mapping is used

Limits worth knowing

Half-cell mapping shows the probability that corrosion is active, not how much steel has been lost or how fast it is corroding. It is less reliable on epoxy-coated or galvanized bars, through coatings and membranes, and on very dry or saturated concrete, and it needs continuous reinforcement. That is why it is one part of a corrosion condition assessment, not a stand-alone answer.

FAQ

Frequently asked questions

Can half-cell testing tell me how much steel has been lost?

No. It shows the probability that corrosion is active. Exploratory openings at the locations the map points to show the actual condition of the bars.

Do you need to remove tile or coatings?

Readings need direct contact with the concrete. On tiled or coated surfaces we make small test points, or test from an uncoated face such as the underside of the slab.

Can you test an occupied building?

Yes. The equipment is portable and quiet. Residents only need to give short access to the areas being tested.

Plan the repair on measured data

One site visit, then a fixed proposal. Testing across Miami-Dade, Broward and Palm Beach, the rest of Florida and the New York Tri-State Area.